Question

Output LED comes on but nothing happens in the field, what could be the problem?

Answer

a. Discrete outputs on a D0-06DD1 model, needs to have V+ terminal connected to 24vdc or positive voltage of DC power source.
b. Discrete outputs on a D0-06DD2 model, needs to have C0 terminal connected to 0vdc of DC power source.



FAQ Subcategory: Power, I/O, and Wiring

This item was last updated on 2009-03-17
Document ID: 1173


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.