Question

Outputs are not turning on in an option module. What could cause this?

Answer

The first input of an optional input module starts at X100. First output of an optional output module starts at Y100.

Page 2-15 covers optional module IO mapping. D0-OPTIONS-M

You can also get information under "PLC >> Configure IO" in the programming software. Look in the slot under the Address In and Address Out column for starting address.

Combo modules require more information found in Options manual. D0-OPTIONS-M


FAQ Subcategory: I/O Modules

This item was last updated on 2021-02-19
Document ID: 1172


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.