Can I configure a DL05 to do high speed counting and generate high speed pulse output?

Answer

You can do High Speed Inputs or High Speed outputs, but not both.
1. Mode 10 allows you to configure one high speed counter, up to 5 KHz.
2. Mode 20 allows you to configure one quadrature counter, which allows counting in clockwise and counter clockwise directions (count up or count down), up to 5 KHz.
3. Mode 30 allows you to do high speed pulse outputs up to 7 KHz. It supports three profiles: trapezoidal, registration and velocity.

Only one of these options for the built in HSIO can be used at a time. More details are in Appendix E of the DL05 User Manual

For applications requiring multiple functions, consider adding an H0-CTRIO2


FAQ Subcategory: High-speed count / Pulse out

This item was last updated on 2021-01-20
Document ID: 1164


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.