AutomationDirect Technical Support
AutomationDirect | Direct Sales in US and Canada | 1-800-633-0405

Pressure Sensors Frequently Asked Questions AutomationDirect Logo


Question

Can I use a ProSense transmitter with your AC drives?

Answer

Yes, all of our AC drives will accept the 0-10v or 4-20mA signals from the ProSense transmitters, but for the GS series, you must use an external DC power supply, typically 24vdc because the 0-10v transmitters need a minimum of 16 volts for their supply.The power supplies on the GS series are only to supply a potentiometer and are extremely small.
The Hitachi SJ300's actually have a 100 mA supply, and will power the transmitters without need of an external supply.


FAQ Subcategory: None

This item was last updated on 2008-12-17
Document ID: 1119


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.


Copyright © 1999- AutomationDirect.com. ALL RIGHTS RESERVED