Question

Can a C-More Micro be used with a CompactLogix CPU?

Answer

Yes, but the EA1 series C-More Micro does not have an Ethernet Port so it must use DF1 or DH485 and use SLC addressing mode. It cannot use Tag Based Addressing.

If you are using a EA1 series 3" C-More Micro you will have to add the EA-MG-SP1 (retired part). The built in com port (RJ12 connector) cannot be used with the AB protocol. You can find more help on how to do that in the C-More Micro Help topic CMM310.Open the help and search for CMM310

Consider using the EA3-S3ML instead.


FAQ Subcategory: None

This item was last updated on 2021-02-17
Document ID: 1097


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.