Question

How can I set the IP address in my WinPLC with Windows Vista, Windows 7 or a Windows Xp PC that cannot use the IPX protocol?

Answer

Unlike Windows Xp, Windows Vista and Windows 7 do not support the IPX protocol that previously was used to reset the WinPlc.

    Alternate means to reset WinPLCs
  1. Insure that you have turned off your PC's firewalls
  2. Power down the rack containing the WinPLC.
  3. Remove the WinPLC and set dipswitch #7 (last to left)to ON
  4. Place the WinPLC back in the rack and apply power. The RUN and POWER LEDs will be flashing.
  5. Use Netedit3 and scan network using TCP/IP
  6. Double click on the WinPLC and change the IP address.
  7. Power down the rack containing the WinPLC.
  8. Return dipswitch #7 to OFF.
  9. Place WinPLC back in the rack and apply power. The RUN and POWER LEDs will not be flashing.


Your WinPLC should now be accessible using the IP address you used above.


FAQ Subcategory: None

This item was last updated on 2012-05-14
Document ID: 1067


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.