Some of the counters and timers are not working in my D3-330 or D3-340. What's wrong?

Answer

This may be the result of using timers and counters with the same number. For example, Timer 600 and Counter 600. The timers and counters share the same memory area in a D3-330/D3-340 CPU. You cannot use the same number for both a timer and a counter.


FAQ Subcategory: CPU & Programming

This item was last updated on 2001-11-07
Document ID: 106


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.