Pushbuttons Frequently Asked Questions
What are the electrical ratings for the contacts on the HT800 30mm pushbuttons contact blocks?
VAC (50/60 Hz) | VAC (50/60 Hz) | VAC (50/60 Hz) | VAC (50/60 Hz) | VDC (1) | VDC (1) | VDC (1) | |
---|---|---|---|---|---|---|---|
Voltage | 120 | 240 | 480 | 600 | 125 | 250 | 600 |
Make and Emergency Interrupting Capacity (A) | 60 | 30 | 15 | 12 | 1.1 | 0.55 | 0.02 |
Normal Load Break (A) | 6 | 3 | 1.5 | 1.2 | 1.1 | 0.55 | 0.02 |
Thermal Current (A) | 10 | 10 | 10 | 10 | 5 | 5 | 5 |
Voltamperes | |||||||
Make and Emergency Interrupting Capacity | 7200 | 7200 | 7200 | 7200 | 138 (2) | 138 (2) | 138 (2) |
Normal Load Break | 720 | 720 | 720 | 720 | 138 | 138 | 138 |
FAQ Subcategory: None
This item was last updated on 2021-03-02
Document ID: 1028
The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.