AutomationDirect Technical Support
AutomationDirect | Direct Sales in US and Canada | 1-800-633-0405

IEC Contactors and Starters Frequently Asked Questions AutomationDirect Logo


Question

My motor is turned on and off frequently, or used for jogging duty. Should I derate (oversize) the contactor?

Answer

Yes. The published AC-3 ratings are for typical industrial continuous use applications. Jogging or frequent operation will significantly reduce the lifespan of an AC-3 rated contactor. For these applications, you should select a derated (oversized) contactor, and select the overload protection based on the motor's full load current.


FAQ Subcategory: None

This item was last updated on 2004-02-17
Document ID: 1027


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.


Copyright © 1999- AutomationDirect.com. ALL RIGHTS RESERVED