Question: I have a new F2-DEVNETS-1 module, but the Think 'N' Do ConnectivityCenter (or IOView) displays an error upon connection. What is causing this error? |
Answer: The F2-DEVNETS-1 is a newer model of the F2-DEVNETS module. In order for this module to be used in versions Live!v5.5 or before, or Studio v7.1 or before, you must put the module in the F2-DEVNETS compatibility mode (See appendix E in the F2-DEVNETS-1 manual). |
FAQ ID: 953 |
Question: What causes a blinking run light on a D2-CM module? |
Answer: The 'Run' light on the CM module will blink for only a couple of reasons
You cannot update the FW in the EM or CM modules |
FAQ ID: 1316 |