Question: Will the D3-350 support the D3-04AD?
Answer: Yes, but only by using the multiplex method. You cannot use the pointer method and the PV direct access for the PID control because of the slow response of this module.
FAQ ID: 353
Question: Will the D3-350 support the D3-02DA?
Answer: Yes, but only by using the multiplex method. You cannot use the pointer method and the control output direct access for the PID control because this module has only 8 bit resolution.
FAQ ID: 354