AutomationDirect Logo EZText Panels Frequently Asked Questions


« Return to the FAQ index

Question I just loaded a new project to my EZ Text panel and none of my Local or PLC messages work but, all other functions of the panel work fine.
Answer
  1. If you have new software V2.0 (which requires firmware ver.B.0 in the panel) and old firmware in the panel everything but the messages will work.
  2. If you have old software I.E.(V1.03)and a new panel that has firmware ver.B.0 in it the messages will not work but everything else will.
    Basically the firmware version in the panel must match the EZ Text software version.

FAQ Subcategory:

This item was last updated on 07-28-2009
Document ID: 942


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.