AutomationDirect Logo IEC Contactors and Starters Frequently Asked Questions


« Return to the FAQ index

Question Can the contactors/starters be used for DC motors?
Answer No. All of our starters and contactors have IEC AC utilization ratings of AC-1 (non-inductive or slightly inductive loads) and AC-3 (inductive loads like induction motors), but no DC ratings. Under IEC 60947-2, -3, -4, and 5, The Categories for DC rated low voltage switchgear and control gear are clearly defined. The reasons for not using an AC rated contactor in a DC system: 1.) Not specified by the manufacturer. 2.) The device does not monitor the DC voltage the same way. 3.) The make or break ratings are different in DC applications. 4.) No arc suppression.

FAQ Subcategory:

This item was last updated on 02-17-2004
Document ID: 924


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.