| Question | What is the accuracy of the timer instructions? |
| Answer | The accuracy of the timer instruction is the same as the accuracy of the clock generator used for the microprocessor in the DL105. The accuracy of the clock generator is ± 50 PPM. So the accuracy of the timer instruction is: ±50 PPM * 60 sec * 60 min * 24 hr = ±4.32 seconds (per day) |
FAQ Subcategory:
This item was last updated on 11-07-2001
Document ID: 42
The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.