AutomationDirect Logo DL405 Frequently Asked Questions


« Return to the FAQ index

Question Does the D4-RM have to be at the end of the chain or can it be wired in the chain (i.e., with slaves at each end)?
Answer The D4-RM does need to be at one end of the physical connection chain. A termination resistor is also required here and at the last slave (which is added by jumpering T to 1).

FAQ Subcategory:

This item was last updated on 11-07-2001
Document ID: 141


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.