Question Can the SOLO Ramp/Soak function be turned on remotely from an external input?
Answer Yes. If you use the SOLO 4896 or 9696 models you can use Event Input 1 to enable or disable your Ramp/Soak operation. If Event Input 1 is closed ( a contact is closed between terminal #3 SG and terminal #4 Ev1) the output will be disabled and the Ramp/Soak operation will cease its operation. Upon opening the contact between SG and Ev1 the Ramp/Soak will start its operation again at Step 0. It will not resume operation of the Ramp/Soak table from the point the contacts were closed.

FAQ Subcategory:

This item was last updated on 11-05-2009
Document ID: 1267


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.