Question Is it true you need to add some form of protection when using relay outputs to turn on solenoids or motor contactors?
Answer a. Yes, it is true. Devices with coils, inductive loads, driven by a PLC relay output will generate a voltage spike when it is turned off. b. You should install some form of surge suppression, such as TVS, MOV or Diode, at the coil or as close to the coil of the solenoid (or other device) as possible. c. This is covered in Chapter 2 starting on page 21 of the DL06 user manual. Click here for Chapter 2 of DL06 User Manual.

FAQ Subcategory:

This item was last updated on 03-18-2009
Document ID: 1178


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.